Input-Modul
I0...I7
4
3
1
1
2
5
4
3
AVENTICS | CANopen | R412005742–BDL–001–AD
6.3.5

Connect the 8x input/output modules

Freely accessible conductive parts
Risk of electric shock on contact!
When connecting peripheral devices (I/O interface), observe
O
the requirements to protect against accidental contact in
accordance with EN 50178, classification VDE 0160.
1. Wire the inputs according to Tab. 8 (DI8_M8) or Tab. 9
(DI8_M12).
2. Connect the electrical inputs/outputs to the I/O modules
with M8 or M12 coupling plugs (accessories).
3. To ensure the IP65 protection class, close unused sockets
with M8 or M12 protective caps (accessories).
The total current for all sensor supplies (pin 1) on one valve
system must not exceed 0.7 A.
Table 8:
Input assignment for 8x input module,
DI8_M8, M8x1 socket
Pin
Signal
1
SENSOR+
3
SENSOR–
4
I0 bis I7
Housing
Table 9:
Input assignment for 8x input module,
DI8_M12, M12x1 socket, A-coded
Pin
Signal
1
SENSOR+
2
I1, I3, I5 or I7
3
SENSOR–
4
I0, I2, I4 oder I6
5
NC
Housing
CAUTION
Assignment
Sensor supply +
Reference potential
Sensor signal
Connected to shield potential
Assignment
24 V sensor supply
Sensor signal
GND reference potential
Sensor signal
Not assigned
Connected to shield potential